ICB series battery energy storage system is specially designed for the commercial and industrial energy storage and EV charging energy storage applications. It offers two solutions: one with a rated power of 218kW and a capacity of 218kWh, optional 30kW solar power input; the other with a rated power of 120kW and a capacity of 241kWh, optional 30kW/60kW solar power input.
218kWh BESS
Description
Additional information
AC grid access | AC voltage: 266Vac-437Vac, 45-65Hz/3-phases+(N)+PE |
---|---|
Solar power access | ICB218kWh-218kW: 0 |
Inner battery groups | Battery group access: 1 group |
STS cabinet (optional) | STS configuration: 250kVA/500kVA |
Parallel configuration | On-grid: |
Electric isolation | Non-isolation for PCS, isolation for PV DCDC |
Metering | AC grid main side: 1 bi-directional AC energy meter |
EMS | Local EMS: IMMU2 EMS controller, inner EMS algorithm and big data |
Insulation detection | Each battery channel and each PV channel, +/PE and -/PE detector |
HMI | Inner 7" TFT touch screen, 5 status LED, E-STOP, battery fire alarm light/beeper |
Dimensions | W * H * D mm = 1100 * 2400 * 1350 mm; weight: < 2800 kg |
Protection level | IP67 for battery pack, IP55 for cabinet |
EMC/EMI | IEC61000-6-2/-4 |
Safety certification | EN62477-1, EN 62109-1/-2, IEC62619, IEC63056, UL9540A |
Grid connection | EN50549-1/2/-10, VDE-AR-N 4110, UNE217001, CEI 0-16 |
Fire protection | Completely submerged aerosol fire extinguishing system, water fire interface, optional pack level active perfluorohexanone firefighting |
Fire sensors | Smoke detector + variety of combustible gas detector |
Environment sensor | Water sensor + temperature sensor + humidity sensor + door access sensor |
Safety design | Explosion-proof board configuration and fire-proof spread structure design, emergency fan |
Energy storage battery | ICB218kWh-218kW: Liquid-cooled battery cluster, 218kWh, 768V (672V~864V), 285Ah, rated 1P charging/discharging |
Battery pack | ICB218kWh-218kW: Liquid-cooled battery pack, 153.6V, 285Ah, 43.7kWh, UL9540A certification |
High voltage control box | Infypower high voltage control box |
Battery BMS | Infypower 2 level BMS structure: battery pack BSU + high voltage control box BMU |
Thermal management | ICB218kWh-218kW: Infypower liquid-cooled unit, 8kW refrigerating and 2.5kW heating capacity each. Full Infypower design and manufacture |